Carrier WEATHER MASTER 48P2 User Manual

Page 16

Advertising
background image

16

Step 8 — Connect Condensate Drain —

There

are a total of five drain connections required on each unit: one

primary drain (on right-hand side of the unit) and four second-

ary drains (two on each side of unit).
PRIMARY DRAIN — The primary drain is a 2-in. FPT pipe

connection located on the right-hand side of the unit looking at

the unit from the return air end. See Fig. 12-21. Fig. 22 shows

the additional length of units with an extended chassis.

With field-supplied fittings and pipe sections, plumb the pri-

mary condensate drain to the 2-in. FPT connector on the base

rail. Use a trap height of at least 4-in. for size 030-070 units

and 7-in. for size 075-100 units. See Fig. 23 and 24. Install with

a height dimension of at least 2-in. from the top of the exit pipe

from the trap section to the bottom of the connector. Apply a

bead of RTV or similar sealant around the pipe joint at the con-

nector in the base rail.
SECONDARY DRAINS (Units Installed on

Curb) — There are two secondary drain connections on each

side of the unit. See Fig. 25. There are secondary drains on

each side of the unit in the filter section and on each side of the

unit in the supply fan section. There are labels marking each lo-

cation on the unit base rail. See Fig. 12-21.

Locate the four 1

1

/

4

-in. drain coupling assemblies and

mounting screws (shipped in a bag taped to the basepan in the

supply fan section, located behind the access panel marked

FAN SECTION). The drain couplings are a 10-gage plate with

a 1

1

/

4

in. half coupling welded to the plate.

At each secondary drain hole location, there is a 1

3

/

8

-in.

hole pre-drilled in the bottom of the base rail, surrounded by

four 0.20-in. engagement holes. Install a drain coupling assem-

bly using screws provided at each secondary drain hole loca-

tion. See Fig. 26. Do not attach any drain coupling assemblies

in the condenser section base rail.

Using field-supplied fittings and pipe sections, assemble U-

traps at each secondary drain fitting. See Fig. 27. Provide a

minimum size of ½-in. pipe for secondary drains. Use a trap at

least 4-in. deep for size 030-070 units and 7-in. deep for size

075-100 units. Apply a bead of RTV or similar sealant around

the drain assemblies.

Consult local plumbing codes for direction on joining multi-

ple drain lines. Total size of any combined line does not need

to exceed nominal 2-in. size of primary drain connection.

Fill the U-traps at the secondary drain locations prior to unit

start-up. Also check the U-traps before each cooling season to

ensure the traps are filled and functioning properly.
SECONDARY DRAINS (Units Installed on Steel Beam or

Slab) — There are two secondary drain connections required

on each side of the unit. There are secondary drains on the bot-

tom of the base rail on each side of the unit in the filter section

and on each side of the unit in the supply fan section. There are

labels marking each location on the unit base rail. See Fig. 12-

21. Drain holes will need to be drilled in these locations at the

side of the base rail. The existing secondary drain holes in the

bottom of the base rail must be sealed. Prior to final positioning

of the unit, apply a bead of RTV or similar sealant around each

secondary drain hole in the bottom of the unit base rail. See

Fig. 27. Install the metal seal plates then position the unit into

final location.

3

1

4

3

2

Fig. 8 — Gasket Location on Roof Curb (48P075-100 Units with Optional High-Capacity Power Exhaust)