Table 20 — Electrical Data — 48P2,P3,P4,P5090 Standard Units

LEGEND

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER EXHAUST

POWER SUPPLY

No. A1

No. B1

Min

Max

Qty

RLA

(ea)

LRA

(ea)

Qty

RLA

(ea)

LRA

(ea)

Qty

FLA

Hp

FLA

Qty

Hp

(ea)

FLA

(ea)

MCA

FUSE OR HACR

BRKR*

460

414

508

3

23.1

150

3

23.1

150

6

3.3

(ea)

30

40.0

208.4

225

2

5

7.6

223.6

250

2

7.5

11.0

230.4

250

2

10.0

14.0

236.4

250

40

52.0

223.4

250

2

5

7.6

238.6

250

2

7.5

11.0

245.4

250

2

10

14.0

251.4

300

50

65.0

239.7

300

2

5

7.6

254.9

300

2

7.5

11.0

261.7

300

2

10

14.0

267.7

300

60

77.0

254.7

300

2

5

7.6

269.9

300

2

7.5

11.0

276.7

350

2

10

14.0

282.7

350

75

96.0

278.4

350

2

5

7.6

293.6

350

2

7.5

11.0

300.4

350

2

10

14.0

306.4

400

575

518

632

3

19.9

109

3

19.9

109

6

2.6

(ea)

30

32.0

175.0

200

2

5

6.1

187.2

200

2

7.5

9.0

193.0

200

2

10.0

11.0

197.0

225

40

41.0

186.3

225

2

5

6.1

198.5

225

2

7.5

9.0

204.3

225

2

10

11.0

208.3

225

50

52.0

200.0

250

2

5

6.1

212.2

250

2

7.5

9.0

218.0

250

2

10

11.0

222.0

250

60

62.0

212.5

250

2

5

6.1

224.7

250

2

7.5

9.0

230.5

250

2

10

11.0

234.5

250

75

77.0

231.3

300

2

5

6.1

243.5

300

2

7.5

9.0

249.3

300

2

10

11.0

253.3

300

FLA

Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration
Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps