Calibre UK IC Communication Adapter ICA93LV User Manual

Page 19

Advertising
background image

Revision 1.7

Page 18 of 27

09/12/1999

getstatus

Function specification:

Int getstatus ( )

Parameters returned

I

2

Cstatus, the current value of the bus status.

Prerequisites

Adapter must be configured using setup.

Functional description

The function reads status word from the adapter and returns it.

recover

Function specification:

Int recover

Parameters returned

ErrCode. If the bus recovery failed error code 8006H is returned
otherwise the status is returned.

Prerequisites

Adapter must be configured using setup.

Functional description

This function issues two consecutive stop commands on the bus, with a
delay in between. It then clears the adapter registers and reads the
status. This should normally set the adapter into a known idle state when
a bus error or other problem has occurred.

If the status does not indicate bus free or the Bus Error bit is still set then
8006H is returned otherwise the status is returned.

sendbytes

Function specification

Int sendbytes (int far *transferarray)

The far pointer must point to a single dimensional array the format of which is detailed below. The calling
function must have initialised elements 0, 1 and 2 prior to calling the function.

Element no

Element name

Description

0

slaveaddress

Slaveaddress is the address to be accessed via the I

2

C

Bus, this is in hexadecimal e.g. A0H.

1

wordaddress

Wordaddress is the offset within the slave to which the
first byte of data is to be written, see transmission format
for more details.

2

nobytes

The number of bytes (n) to be sent. Min value 1.

3

byte 0

First byte to be sent.



byte n

Last byte to be sent.

Parameters returned

bsent, the number of bytes actually sent.

Prerequisites

Adapter must be configured using setup. Array elements 0, 1 and 2
must be initialised. Usually elements 3 to n would also be initialised.
Array must be pre-defined to a size at least large enough to hold all the
parameters and data concerned.

Transmission format

There are two transmission formats, these are:

i. start-slaveaddress-byte(s)-stop

If transmission format i.) is required set the wordaddress to a number greater than FFH.

ii. start-slaveaddress-wordaddress-byte(s)-stop

If transmission format ii.) is required set the wordaddress to a number less than or equal to FFH.

Functional description

The function determines the required transmission format and then
sends a start code and the slave address. If transmission format ii) has
been selected the wordaddress is sent.

The data bytes are then transmitted sequentially.

Should a time-out occur or he slave not acknowledge a transfer the
transmission is terminated by a stop and the number of bytes actually
transmitted is returned.

Advertising