NOTE: Outside the standard operating temperature

(10 °C to 35 °C), the system can operate down to –5

°C or up to 45 °C for a maximum of 1% of its annual

operating hours.

For temperatures between 40 °C and 45 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per 125

m above 950 m (1 °F per 228 ft).

Expanded Operating Temperature Restrictions

Do not perform a cold startup below 5 °C.

The operating temperature specified is for a

maximum altitude of 3050 m (10,000 ft).

Four redundant power supplies are required.

Non Dell qualified peripheral cards and/or peripheral

cards greater than 25 W are not supported.

NOTE: For more information on the server module-

specific restrictions for the expanded operating

temperature range, see the technical specifications

in the server module Owner's Manual at dell.com/

poweredgemanuals.