Chicago Pneumatic CPVS 40 User Manual

Page 18

Advertising
background image

Chicago Pneumatic Compressors

62 305 258 65

01/2008
Page 18

• Pressure regulation for low rates of flow

For an air consumption rate lower than the minimum rate of flow
for the machine, the pressure is adjusted by the machine's time-
delayed START/STOP controls.

Since the operation element cannot function below a certain speed
(corresponding to the minimum output), the compressor conti-
nues to run and compress at the minimum speed until the pres-
sure reaches the limit called "Indirect shutdown ".
Once this threshold has been reached, the motor will stop, the
machine will go into stand-by mode after a certain period of
inactivity and the full drainage process will be carried out.The
pressure then drops towards the indicated pressure and, at the
end of the minimum time delay (since reaching the no-load pres-
sure), the drive allows the motor to restart. The pressure then
rises again and the cycle starts over (fig. 14 d).
To avoid pumping the system - frequent stop / start - drainage
time may be increased
(cf. notice AIRLOGIC).

Fig. 14a

The principle of the pressure regulation by variable speed

• Energy saving

For demand of compressed air within the machine's flow range -
min flow to max flow, the frequency converter or the variable
speed drive feed the motor in order to ensure that it turns at the
speed required to supply air demand both for pressure and flow.

It is used to adjust the power supply to the motor (and thus the
machine) to the exact power requirement for the compression of
the air, without a drainage stage being necessary.

COMMENT :
Energy savings are increased if machine maintenance is carried out
in accordance with the maintenance instructions and frequency.

Controller

Pressure

required

Drive

Motor

Compressor

unit

Tank

System

Pressure sensor

Frequency speed

Advertising
This manual is related to the following products: