Chicago Pneumatic CPVS 40 User Manual

Page 3

Advertising
background image

Chicago Pneumatic Compressors
62 305 258 65

01/2008

Page 3

CPVS Model

40

50

60

75

Motor power

(hp)

40

50

60

75

Main Voltage 460 Volt / 3 / 60 Hz

Nominal current

(A)

69

81

89

125

Power supply cable

AWG 4

AWG 3

AWG 1

AWG 0

Fuse protection

(Type RK5)

80

100

125

150

Connection of the electric plate to an external control box

• Install an RC filter on the KM1 coil.
• Install an RC filter on the KM2 coil.
• All connections between external parts and the compressor must be carried out using a shielded cable, which must be grounded at one of its

ends.
WARNING: the operation connection cables between the different elements must never follow the same path as the existing power
cords. A separate installation from the power cords must be carried out.

• Install an RC filter on all the relay coils of the external operation units.

Advertising
This manual is related to the following products: