Piping circuits – Taylor-Wharton EF-450 User Manual

Page 7

Advertising
background image

PIPING CIRCUITS


The following paragraphs describe the operation of the piping circuits of the system. The descriptions refer to
the main components of each circuit and are grouped by function. Reference the piping schematic below and
in the general arrangement drawing for the component designations. These component and circuit
descriptions should be understood before attempting operation.

VC-1

CV-1

FSV-1

CV-2

V-5

V-4

V-3

V-1

LI-1

PI-1

R-1

R-2

V-2

SV-1

SV-2

PBC-1

PCV-1

CN-2






CN-1

CN-3


CN-4
















Legend

CN-1

Connection, Liquid Fill / Withdrawal

LI-1

Liquid Level Gauge

CN-2

Connection, Full Trycock & Vent

PI-1

Pressure Gauge

CN-3

Connection, Pump / Top Fill

PBC-1

Pressure Building Coil

CN-4

Connection, Gas Withdrawal

VC-1

Vaporizer Coil

V-1

Valve, Liquid Fill / Withdrawal

PCV-1

Pressure Building Regulator

V-2

Valve, Full Trycock / Vent

SV-1

Safety Valve

V-3

Valve, Gas Withdrawal

SV-2 *

Safety Valve, 22 psig

V-4

Valve, Pressure Building

R-1

Safety Disc

V-5 *

Valve, Isolation

R-2

Outer Casing Safety Disc

CV-1

Pump / Top Fill Check Valve

FSV-1

Fill Stop Valve

CV-2 **

Secondary Pump / Top Fill Check Valve

Notes:
*

Featured on DOT models only.

**

500 psi vessels feature a ball valve, ½” FNPT instead of the check valve.

Figure 1: System Piping Schematic

7

Advertising