3

Exhaust tube

Rubber
gasket

Cover gasket

(ordering option)

Sensor housing
and electronics

Rubber gasket

Sensor cover

Plug

Sampling tube

Collar

Power
Dirty

Trouble
Alarm

LEDs

Smoke Sensor

Fastener

(2X)

Controller cover

Conduit nuts

( field supplied )

Conduit support plate

Cover gasket

(ordering option)

Conduit couplings

Terminal block cover

Controller housing

and electronics

Power

Trouble

Alarm

LEDs

( field supplied )

Smoke Control Module

C07173

Fig. 2

--- Smoke Detector

SMOKE CONTROL MODULE

RETURN SMOKE SENSOR

A1

B1/A2

C1/B1

PLUG LOCATION

C07174

Fig. 3

--- Return Air Smoke Detector Location

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury and/or death.
Prior to installation of this accessory, make sure all

power is disconnected to the unit and locked out and

tagged.

!

WARNING

NOTE: For horizontal applications it is easiest to install the
smoke detector prior to making duct connections.

1. Open the hinged electrical/compressor access door and

secure.

2. Find the 2 plugs located above compressor B1/A2,

remove and discard. Cut holes in the insulation located be-

hind the partition.

3. Remove cover from smoke detector. The screws will

remain captured in the cover.

4. Slide exhaust tube into the sensor. The exhaust tube

should be inserted from the back of the sensor, into the
hole with four slots, and locked into place. (See Fig. 2.)

5. Slide smoke detector into holes in partition with the

ter-

minal block to the right. Do not secure at this time.

6. Slide the sampling tube collar over the sampling tube un-

til the tabs lock into the tube. (See Fig. 2.)

7. Slide long sampling tube (P/N RN20ZT060) into left--

hand hole of smoke detector. It might be necessary to tilt
the smoke detector upwards in order to properly align the

sampling tube, making sure that the sampling holes

point DOWN. (See Fig. 4.)

8. Install plug into far end of sampling tube.
9. Remove the unit side panel at the return end of the unit.

Save screws for use later.