5

SAMPLING TUBE
SUPPORT BRACKET

C07176

Fig. 5

--- Sampling Tube Support Bracket

CUT OFF CONNECTOR, LABELED TB3-5, ON ORN WIRE

PL19

C07177

Fig. 6

--- Return and Supply Air Smoke Detector Wiring on ComfortLink Units

Supply Air Smoke Detector Installation

(CRSMKSUP001D00)

The supply air smoke detector is to be installed in the predrilled
holes located on the front of the first indoor blower. (See Fig. 9.)

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury and/or death.
Prior to installation of this accessory, make sure all

power is disconnected to the unit and locked out and

tagged.

!

WARNING

1. Open the indoor fan access door and secure.
2. Open and secure hinged electrical/compressor access door.
3. Disconnect wires located on the right-hand side of the fan

deck. On gas heat units, the indoor fan plug and the limit
switch quick connects must be disconnected. On units

without gas heat, only the indoor fan plug must be
disconnected.

4. Find the 2 plugs located in the blower side plate. Remove

the plugs and discard. It will be necessary to remove some
of the tape holding the plugs in place.

5. Remove cover from smoke detector. The screws will

remain captured in the cover.

CR

S

M

K