Fault code 24 – Carrier 58MVP User Manual

Page 19

Advertising
background image

Fault Code 24

SECONDARY VOLTAGE FUSE IS OPEN—Indicates fuse is open and there is a short in low-voltage wiring.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel.

2

2.

Is secondary voltage fuse blown? Check continuity to make sure.

5

3

3.

Replace furnace control board.

4

4.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

INDEX

5.

Disconnect all thermostat leads from furnace control board (including HUM terminal) and replace
secondary voltage fuse.

6

6.

Depress door switch. Use a piece of tape to hold switch closed.

7

7.

Does Fault Code 24 flash?

8

10

8.

You have a short circuit in limit switch circuit. This includes limit switch, flame rollout switch, and
auxiliary limit switch.

9

9.

Fix problem and replace secondary voltage fuse if necessary.

4

10.

Jumper R and W/W1 thermostat terminals on furnace control board.

11

11.

Does Fault Code 24 occur when W/W1 is energized?

12

16

12.

Disconnect jumper wire across R and W/W1 thermostat terminals and replace secondary voltage
fuse.

13

13.

Disconnect PL2 from furnace control board and jumper R and W/W1 thermostat terminals on fur-
nace control board.

14

14.

Does Fault Code 24 occur when W/W1 is energized?

3

15

15.

You have a short circuit in pressure switch circuit.

9

16.

Does Fault Code 24 occur when low-pressure switch is energized?

17

20

17.

Disconnect PL2 from furnace control board.

18

Table 2—Air Conditioning (A/C) Airflow Setup Switch Position

AIR CONDITIONER

(TONS)

AIRFLOW

(CFM)

A/C SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

A/C-1

A/C-2

A/C-3

040

060

080

080

100

120

Default

1200 or

2000

OFF

OFF

OFF

3 Tons

1200 CFM

3 Tons

1200 CFM

3 Tons

1200 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

1-1/2

600

ON

OFF

OFF

X

X

X

2

800

OFF

ON

OFF

X

X

X

X

X

X

2-1/2

1000

ON

ON

OFF

X

X

X

X

X

X

3

1200

OFF

OFF

ON

X

X

X

X

X

X

3-1/2

1400

ON

OFF

ON

X

X

X

X

X

X

4

1600

OFF

ON

ON

X

X

X

5

2000

ON

ON

ON

X

X

X

X—Indicates allowable selection.

Table 3—Continuous Fan (CF) Airflow Setup Switch Position

CONTINUOUS FAN

(CFM)

CF SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

CF-1

CF-2

CF-3

040

060

080

080

(5 Ton)

100

120

Default

OFF

OFF

OFF

565*

515*

690*

690*

860*

1035*

600

ON

OFF

OFF

X

X

X

800

OFF

ON

OFF

X

X

X

X

X

X

1000

ON

ON

OFF

X

X

X

X

X

X

1200

OFF

OFF

ON

X

X

X

X

X

X

1400

ON

OFF

ON

X

X

X

X

X

X

1600

OFF

ON

ON

X

X

X

2000

ON

ON

ON

X

X

X

* Add 15% additional CFM when Bypass Humidifier switch SW-3 on control board is used.
X—Indicates allowable selection.

Table 4—Two-Speed AC/HP Airflow Requirements (CFM)

OUTDOOR UNIT CAPACITY

036

048

060

A/C Setting

3 Tons—1200

4 Tons—1600

5 Tons—2000

CF Setting

800

1000

1000

19

Advertising