MEP-4200/4500/4900 Series

2

Installation Guide

Wiring

Depending on the model, signal/power wiring might

be to terminals under the conduit fitting or to color-

coded wires in the attached cable. See Illustration 2.

Consult the model label and the appropriate wiring

shown in Illustrations 3 through 8.
For auxiliary switch wiring and setting, see

Auxil-

iary Switch (MEP-4x7x) on page 3

.

For models withOUT the attached signal/power

cable:
1. Loosen the screw on the

conduit fitting and lift up

to remove the fitting.

2. Using a utility knife or drill, cut the red plug

to accept wiring or replace the plug with an

application-specific fitting.

NOTE: The red plug (or similar fitting) protects

internal components from debris, helping

to ensure long actuator life.

Power/Signal

Terminal Block

Selector

Switches

Power/Signal

Cable

Aux. Switch

Cable

(Under Conduit Fitting)

Illustration 2—Cables and Terminal Block Options

Illustration 3—MEP-4xx2 Proportional Control

~/+

+

Control Signal

2–10 VDC

Power Supply

24 VAC/VDC

OUT (Green)

2–10 IN (White)

T

COM (Blac

k)

~24

V (Red)

+

Feedback Output
1–5 or 2–10 VDC

Illustration 4—MEP-4x51 Tri-State Floating Point Control

Power Supply

24 VAC/VDC

CW

CCW

T COM

~24 V

~/+

Switch

Position

1 2

Illustration 6—MEP-4x51 2-Position Control (4-Wire), CW Leg

Power Supply

24 VAC/VDC

Contact Position:

Closed = CW Rotation

CW

CCW

T COM

~24 V

~/+

Open = CCW Rotation

Switch Position

1 2

Illustration 5—MEP-4x51 2-Position Control (4-Wire), CCW Leg

Power Supply

24 VAC/VDC

Contact Position:

Closed = CCW Rotation

CW

CCW

T COM

~24 V

~/+

Open = CW Rotation

Switch Position

1 2

3. Thread wires through the plugged opening and

connect to the terminal block according to the

relevant model and application.

4. For MEP-4xx2 models, adjust the feedback

voltage, direction, and automapping as needed.

See

Direction, Feedback, and Auto-Mapping

(MEP-4xx2) on page 4

. For MEP-4x51

models, adjust the selector switch as shown in

Illustrations 2 and 4–6.

5. Reinstall the conduit fitting and tighten the screw.
NOTE: After initial power-up, proportional models

have a 30-second delay of motor operation.

CAUTION

ATTENTION

Risk of electrical shock.
Disconnect ALL power
before servicing. More than
one disconnect provided
on models with auxiliary
switches. Failure to follow
electrical safety precautions
with live electrical
components could result in
injury or death.
If both conduit connections
are used, they MUST be
externally connected during
installation. The nonmetallic
enclosure does not provide
grounding connection
between the two conduit
connections.

Risque de choc électrique.
Débranchez l’alimentation
avant l’entretien. Plus d’un
sectionneur fourni sur les
modèles avec contacts
auxiliaires. L’inobservation
des consignes de sécurité
électrique avec des
composants électriques sous
tension peut entraîner des
blessures ou la mort.
Si les deux entrées de câble
sont utilisés, ils doivent être
connectés en externe lors de
l’installation. Le boîtier non-
métallique n’assure pas la
connexion à la terre entre les
deux connexions.