Fail-safe direction, Auxiliary switch (mep-4x7x), Auxil – KMC Controls MEP-4900 User Manual

Page 3

Advertising
background image

MEP-4200/4500/4900 Series

3

Installation Guide

Illustration 7—MEP-4xx4 Two-Position (2-Wire) 24 VAC/VDC

Illustration 8—MEP-4xx5 Two-Position (2-Wire) 100–240 VAC

Illustration 10—Actuator Rotation and (MEP-497x) Aux. Switch

Auxiliary Switch (MEP-4x7x)

In MEP-4x7x models, the adjustable auxiliary SPDT

switch can be set to trip anywhere between 0° (full

CW rotation position) and 90° (full CCW). To adjust

the auxiliary switch position:
1. While pressing the gear disengagement lever (see

Illustration 1), rotate the actuator to the point

where the auxiliary switch should trip.

2. Using a small, flat-bade screwdriver, adjust the

rotary dial to “0” (see Illustration 10). As the

Auxiliary Switch Cable*

Wire Color

Function

Red

Adjustable Aux. Switch, Common

Blue

Adjustable Aux. Switch (see Illustration 10)

Black

Adjustable Aux. Switch (see Illustration 10)

Brown**

Fixed Aux. Switch, Common

Orange**

Fixed Aux. Switch, Closed 0–10°

Yellow**

Fixed Aux. Switch, Closed 11–90°

*Left-hand cable, looking from the top (see Illustration 2).
**Fixed auxiliary switches (with brown, yellow, orange wires) are
only available in MEP-497x models.

Illustration 9—Fail-Safe Direction Switch Dial

Fail-Safe Direction

All models offer selectable fail-safe direction. Pro-

portional and tri-state models also offer the option

to turn the fail-safe off (see Illustration 9). Using a

small, flat-bade screwdriver, adjust the switch dial to

the desired clockwise or counterclockwise direction.

NOTE: After initial connection or reconnection to

power on MEP-4xx2 proportional models,

proper fail-safe operation might be delayed

up to 30 seconds (until the capacitors are

fully charged).

Line/Hot
Neutral

(L1) Neutral (Blac

k)

(L2) Line (Red)

100–240 VAC Power

NOTE: Double Insulated. Meets UL

requirements without the need

of an electrical ground connection.

Power Supply

24 VAC/VDC

T COM (Blac

k)

~24

V (Red)

~/+

Rotation

Indication

(0–45°)

Auxiliary

Switch

Setting

Dial

Actuator Shown

At 45° Rotation

Rotation

Indication

(45–90°)

actuator rotates, the switch dial arrow will point

to the current switch position (Red connected to

Blue vs. Red connected to Black). For example,

if the switch is set to trip (dial at “0”) when the

actuator rotation position is at 45°, then Red is

connected to Black from 0° to 45°, and Red is

connected to Blue from 45° to 90°.

NOTE: On MEP-497x models, a second switch is

fixed at 10° from full CW direction (Brown

is connected to Orange in the 0–10° range,

and Brown is connected to Yellow 11–90°).

3. Wire the desired auxiliary device(s) to the cable.
NOTE: For more detailed information, see the

MEP-4xxx Application Guide

on the KMC

web site.

NOTE: The SPDT switch is rated for 6 A with resis-

tive load or 3 A with motor load @ 250 VAC.

Advertising
This manual is related to the following products: