VEZ-41/44 Series, 2-Way/3-Way, NPT, Pneumatic Zone Control Valves

2

Installation Guide

Diverting

As the valve stem moves downward, the flow

through VCZ-44 ports AB-A decreases and the flow

through ports AB-B increases. As the valve stem

moves upward, the flow through ports AB-A in-

creases and the flow through ports AB-B decreases. If

there is a loss of signal pressure, the actuator returns

the valve to its normal position—the valve fails with

flow to port A.

Mixing

The three-way VCZ-44 zone valves are diverting

valves. However, they may be used as mixing valves

when connected in the return flow as shown in the

diagram below and if system and differential pres-

sures are within the gray area of the chart below.

+

Bypass

Coil

Three-Way Valve in Return Flow

B

AB

A

Pressure

(See

Chart)

COM

A

B

AB

14.5 (100)

11.6 (80)

20.3 (140)

17.4 (120)

8.7 (60)

5.8 (40)

4.3 (30)

94 (650)

2.9 (20)

14.5

(100)

29

(200)

43.5

(300)

58

(400)

72.5

(500)

87

(600)

101.5

(700)

116

(800)

130.5

(900)

System Pressure in psi (kPa)

Differential Pressure

in psi (kPa)

Allowable Mixing Applications

3-Way Valve Applications

Connection

Connect the main air supply (30 psi max.) to the 1/8"

NPT port on the top of the actuator.

1/8" NPT

Air Connection

Ring Nut to

Valve Body

1

2

Mounting Actuator on Valve Body

REMOVE Black

Plastic Attachment

Support Ring

if Present