System connections, Thermostats crestron chv-tstat and chv-thstat, Network connection for crestron installer only – Crestron electronic CHV-THSTAT User Manual

Page 12: Backplate

Advertising
background image

Thermostats Crestron

CHV-TSTAT and CHV-THSTAT

System Connections

Backplate - view from the front with the cover removed

TOP

HU

M

RHU

RS

R

RS

R

RS

1

RS

2

24

(C)

24

(R)

24V

Y

Z

G

NETWORK

RH

RC

G

Y/

Y1

Y2

O

B

W/

W

1

W2

Backplate

24(R) - 24 VAC reference terminal. Can be connected to RH or RC

by P4 jumper setting, or tied directly to power source

24(C) - 24 VAC common terminal supplies remote 24 VAC power
to thermostat

RS2 - Remote Sensor terminal - Connect the sensor from RS2 to RSR

RS1 - Remote Sensor terminal - Connect the sensor from RS1 to RSR

RSR - Remote Sensor Returns - Common sensor terminal

RHU - Reference for humidifier

HUM - Energized to RHU during humidity call

W2 - Heat (stage two), energized to RH during a call for

second stage heat in heat/cool systems
W/W1 - Heat (single stage)/heat (stage one) energized to RH

during a call for heat in heat/cool systems or aux heat in

heat pump systems
B - Energized to RC during non-cooling modes

O - Changeover control, energized to RC during cooling modes
Y2 - Compressor (stage two), energized to RC on two-stage

systems on call for second stage
Y/Y1 - Compressor (stage one), energized to RC when

compressor (or first stage) is run
G - Fan, energized to RC during call for fan

RC - Reference Cool, used for calls to cooling system

RH - Reference Heat, used for calls to heating system

Network Connection

for Crestron

Installer Only

8

Thermostats: CHV-TSTAT and CHV-THSTAT

Operations and Installation Guide – DOC. 8163A