CHV-TSTAT and CHV-THSTAT

Other Digital Joins

Signal Name

Symbol

I/O

Definition

GLOBAL_UPDATE_BTN Advanced

Output

Output that is asserted when the global update “send”
button is pressed

MESSAGE_ICON_ON

Advanced

Input

Causes the front panel third text line to flash “view msg”
alternately with “on line/offline,” alerting the user to
check a message that was sent to the thermostat

FRONT_PANEL_LOCKOUT Both

Input Causes the buttons on the thermostat to become

inoperable when asserted, Useful for locking out
changes in operation by users

RUN_BACKLIGHT

Advanced

Input

Triggers the backlight to turn on for its 8 seconds

BTN_PRESS_1_F Advanced

Output

Asserted for the duration that remote button 1 is pressed
(up button, remote page 1)

BTN_PRESS_2_F

Advanced

Output

Asserted for the duration that remote button 2 is pressed
(down button, remote page 1)

BTN_PRESS_3_F Advanced

Output

Asserted for the duration that remote button 3 is pressed
(up button, remote page 2)

BTN_PRESS_4_F

Advanced

Output

Asserted for the duration that remote button 4 is pressed
(down button, remote page 2)

MSG_WAITING_F Advanced

Output

Asserted when an indirect text message is received on
$message join and latched until the user presses the
“CLR” button on the message screen

Humidifier Related Joins (all analog values are in whole %)

NOTE: All humidity-related analog values are input and output as whole numbers. Example: For 47% humidity, the
reading is sent as 47.

Signal Name

Symbol

I/O

Definition

HUMIDIFIER_EN

Both Input

Enables the humidistat operations when asserted
(Digital)

HUMIDIFIER_EN_F

Both

Output

Feedback for above (Digital)

HUM_SETPOINT

Both Input

Analog join that sets the humidity setpoint, 5-70%, all
other values ignored, All values are whole numbers, so
sending 38 changes the setpoint to 38%

HUM_SETPOINT_F

Both

Output

Feedback output so that changes in the value can be
monitored by the control system

OUTDOOR_HUM

Both Input

Input allowing the outdoor humidity value to be
displayed on the "outdoor" page even if the particular
unit does not have an outdoor remote sensor

OUTDOOR_HUM_F

Both

Output

Output for outdoor humidity. It is only active when a
particular unit has a remote outdoor sensor connected
Otherwise, zero is output

INDOOR_HUM

Both Input

Input allowing display of indoor humidity on the front
panel Importing the value this way is required only if
setup was a TSTAT with non-humidity remotes (no way
of measuring indoor humidity) The network input value
is overridden by a measured value if one is available

32

Thermostats: CHV-TSTAT and CHV-THSTAT

Operations and Installation Guide – DOC. 8163A