Type c standard & night setback, Laboratory airflow monitors & controls, Operating principle – Plastec Variable Air C User Manual

Page 3: Led & digital - vav system

Advertising
background image

When the fume extraction fan is running, it causes negative pressure inside

the fume cupboard. If the sash is lowered, the negative pressure become more

intense causing air to be drawn through the sash opening at an increased velocity.

Conversely, if the sash is raised the negative pressure becomes less intense and air

velocity reduces.

If an opening is made in the wall of the fume cupboard, air will enter it at a

velocity determined by the same negative pressure that is drawing air into the

sash opening. By sensing the air velocity through an opening, we can determine

its level at the sash opening.

PLASTEC

®

AirControl Type C exploits this by the placing of a numerical sensor,

or thermal anemometer into a hole in the cupboard and sending the air velocity

measurement obtained to a display on the fascia panel. Based on air velocity
measured, Plastec

®

AirControl C will send a signal to an inverter to either increase

or decrease fan speed.

The air velocity level is displayed on the fascia either by LED illumination or

digital read-out. An audible alarm will also sound if the air velocity is too low.

Operating Principle

SENSOR

Airflow Monitor

www

.plas

tecv

ent.net

2216 60th Drive East • Bradenton, Florida 34203

(941) 751-7596 • Fax (941) 751-7598 •

www.plastecvent.net

3

Laboratory Airflow Monitors & Controls

TYPE C STANDARD & NIGHT SETBACK

LED & DIGITAL - VAV SYSTEM