Important

Connection to PLC Analog Input Module

If the PLC analog input uses a common ground (negative input of the analog card) and both PLC
channels are connected to the same option card, there is crosstalk and the values of the 2 inputs will be
merged.

Example: If one is inputting 6 mA and the other is inputting 12 mA they will merge and each looks like it is
inputting 9 mA.

6 + 12 / 2 = 9 mA

To prevent this cross talk, the PLC must have isolated grounds on the input channels.

Specifications

Resolution

16-bit, monotonicity over temperature

Linearity

±0.03% of full scale input

Current Output

0–20 mA or 4–20 mA (20% offset)

Maximum Load Resistance

840

Power consumption

3.9W (max. load @ 20 mA)

Voltage Output

0–10 VDC

Minimum Load Resistance

1.1 K

Power consumption

3.9W (max. load @ 10 VDC)

Input Protection

Short circuit protection, 300W transient voltage suppression
Protection for ESD, EFT (electrical fast transients), tertiary lightning, and system-generated
transients per IEC 60001-4-2, 60001-4-4, and 60001-4-5; European Standards EN50082
and EN61000-4

230 W. Coleman St. • Rice Lake, WI 54868 • USA

U.S. 800-472-6703 • Canada/Mexico 800-321-6703 • International 715-234-9171 • Europe +31 (0)26 472 1319

www.ricelake.com www.ricelake.mx www.ricelake.eu www.ricelake.co.in m.ricelake.com

Rice Lake Weighing Systems is an ISO 9001 registered company.

© Rice Lake Weighing Systems Specifications subject to change without notice.

© Rice Lake Weighing Systems

December 2014

PN 69089 Rev B

Advertising