PROTECTION DESCRPTION:

Battery Polarity Reverse Protection: when the battery polarity is reversed, the

BATT indicator light will display RED and the BATTERY and LOAD terminals will

terminate output. Battery reverse will not damage the model if the AC power is off.

The AC switch must be turned off at any time when the battery is changed. If AC is

on and the battery is disconnected, the PS polarity reverse protection is disabled, and

if the polarity is reversed, the fuse of the PS will be burnt, sometimes causing a spark.

Battery Low Voltage protection: When the AC is OFF or has failed, if the battery

voltage is lower than 10.7V±0.2V, the model will turn off the output on LOAD.

When AC returns or the battery voltage returns to 12.6V±0.2V, then the output on

LOAD will recover automatically.

Load Over Current Protection: the model will automatically shut down if the load

is over 12A. when the load is reduced, the PS will auto recover.

Load Over Voltage Protection: when the LOAD output is over 18V, the PS will turn

off.

Load Short Circuit Protection: output terminal short circuit will not damage the PS,

it will be simply stop the output. When the short circuit status is removed, the LOAD

will recover immediately.