If you connect a solar panel or wind turbine to the BATTERY terminal at the same

time, if AC failed, when the battery voltage lower than 10.7V, the LOAD output will

turn off, but if the output voltage of the solar panel or wind turbine is higher than the

battery voltage, the battery will be charged by the solar panel or wind turbine, when

the battery voltage is back to 12.6V, the LOAD output will recover automatically.

The maximum load of the PS is around 300W, which means 12A maximum DC

output on LOAD and 12A maximum charge current on BATTERY. If the load draws

12A output, then the charge current will be limited to around 10A, if there is no load,

then charge current may be up to 12A maximum.

The output voltage on LOAD terminal is regulated at 12.2V±0.2V, with over voltage

protection, over current protection and short circuit protection.

The charge voltage for wet battery is 14.6V, floating voltage is 13.2V.

The charge voltage for gel battery is 14.2V, floating voltage is 13.5V

When the charger is in charging mode and charge current is more than 2.5A, the

CHG indicator light will be YELLOW, when charge current is lower than 2.2A, the

charger turns to maintenance mode, the CHG light is off and CHD light is GREEN.

All LED indicators will turn off when AC fails except BATT and battery type

indicator (WET or GEL).

If no battery is connected on BATTERY terminal, then there will be no output on the

terminal.

The cooling fan on the model will operate when the unit is turned on. The speed of

the fan varies depending on the temperature control circuit.