Tycon Power TPDIN-Monitor-WEB User Manual

Tpdin-monitor-web, Qwik install, Web based monitor and control

Advertising
background image

TPDIN-Monitor-WEB

Web Based Monitor and

Control

Remote Power Stations

Backup Power Systems

Solar Systems

Wind Powered Systems

Industrial Sense & Control

Process Automation

Congratulations! on your purchase of the TPDIN-Monitor-WEB

PowerSens™ System Monitor. Please take a moment to review

this Qwik Install Guide before installation.

Recommended Tools and Supplies: Small Flat Blade Screwdriv-

er, 35mm x 7.5mm DIN Rail

Qwik Install

STEP 0:

The TPDIN-Monitor-WEB can be used to monitor Qty 4 1V-

80V Voltages, 4 Currents ( Qty 2 +/- 10A and Qty 2 +20A) and two tem-

peratures (1 internal and 1 external). There are 4 10A relays that can be

used to control power to 4 devices. Two of those relays can be auto-

matically set based on a temperature or voltage value. Two can be op-

erated automatically based on a ping watchdog or time control.
STEP 1:

Install the TPDIN-Monitor-WEB to a suitable DIN rail mount.

STEP 2:

Connect the voltages to be monitored to the V1—V4 voltage

ports. The green connector needs to be removed to be able to access

the wire terminal screws. The green connectors are numbered 1-7 and

should be re-installed back in their proper position. Voltages between 1

and 80volts DC can be monitored.

STEP 3:

Connect the currents to be monitored to the I1-I4 current ports.

I1 and I2 can read currents from 0.1 to 20A. I3 and I4 can read positive

or negative currents to +/-10A. These can be used to measure current

flowing into and out of a battery to see if the battery is charging or dis-

charging. The green connectors may need to be removed to be able to

access the wire terminal screws. The green connectors are numbered

1-7 and should be re-installed back in their proper position.

Advertising