STEP 11:

Open the Control Page. This is where you can set the relay

Ping Control or Time and Temperature or voltage controls. You can set

up the EMAIL server and set various email triggers.

Relays 1 and 2:

Time Control: Set the On time and Off time in 24hr format. Note: Time

control overrides Ping Control and Manual control.

Ping Control: Set the IP Address to ping. Set the ping frequency

(Every). Setting the frequency to zero disables the ping. Set the number

of consecutive Fails before the relay will cycle. Set the Wait so that the

system will wait before pinging again. This is useful to allow the unit that

you are pinging to fully reboot after a power cycle. Example: if you set

the unit to ping every 60 seconds and you have fail set to 2, it will take

approx. 2 minutes before it would see two consecutive failures and then

cycle the relay.

Relays 3 and 4:

Temperature Control: Relay 3 can be controlled by the Internal Tem-

perature and Relay 4 can be controlled by the External temperature

probe. Make sure ON temperature is lower than OFF temperature set-

ting.
Typical Application:

Fan Control: Set ON to 50; Set OFF to 100

Heater Control: Set ON to –40; Set OFF to 20

Voltage Control: Set the relay turn on and turn off voltages. Relay will