Tech corner – Tycon Power TPDIN-Monitor-WEB User Manual

Page 5

Advertising
background image

5

change state when voltage goes outside the range. Temperature set

takes priority.

Email Alerts:

Set the Email server: ie; smtp.1and1.com Note: GMAIL accounts won’t

work because they require SSL security when sending emails.

Set the email account user name and password. Leave user name

blank to force no authentication.

Check the “Use Username as From Field” checkbox (recommended)

to have the emails sent from the username which is usually an email

address. If not checked, the emails will be sent from the email address

entered in the first MAIL To: field.

Enter the destination email addresses in the Mail To: fields. They can

be the same or different depending on your needs.

Select the parameter trigger from the dropdown box on the left.

Periodical: This will send an email of the present readings periodically

based on the number of minutes entered into the Lower/minutes box.

Caution: if you leave set at 0 it will send an email every two seconds

Relay 1-4: These will send an email any time the state of the relay

changes due to some automatic relay control like Ping, Time or Tem-

perature. It won’t send an email when the relay is manually operated.

Relay 1-4 doesn’t require any lower or upper settings. Leave at 0.

Volt Amp and Temp: Just set Lower and Upper values and the system

will send an email anytime the reading is outside the set range. The

frequency of emails is set by the Analog Values Mail Delay time. If the

delay time is set too low you will receive a flood of emails whenever one

of your set parameters fall outside the set range.

TECH CORNER

Additional Information you may find useful

1. FUSE: The TPDIN-Monitor-WEB has an internal 2A fuse. If the

TPDIN-Monitor-WEB doesn’t power up, check the fuse.

2. LIMITS: Don’t exceed 80V on the voltage inputs or 20A on the cur-

rent inputs or 10A on the relays or the unit could be damaged. This kind

of damage isn’t covered under warranty.

3. MOISTURE: The TPDIN-Monitor-WEB is designed to be used in-

doors or outdoors in a weatherproof enclosure. Avoid getting the TPDIN

-Monitor-WEB wet. This kind of damage isn’t covered under warranty.

4. BATTERY STATUS: If measuring voltage of battery systems typical

state of charge readings are as follows. These readings are without any

load on the battery. For max battery life don’t discharge under 50%: