Advanced operation of temperature controller – WineKeeper MAGNUM Series User Manual

Page 10

Advertising
background image

8

The cooling unit is factory preset with a Minimum Set Point of 58°F and a Temperature

Differential of 4°F. This means that the cooling unit will turn on when the display rises

above 62°F (58°F + 4°F), and turn off when the display falls below 58°F. In this example,

the average temperature inside the cabinet will be 60°F.

To view the Minimum Set Point, press the “Set” button for one second. To change the Minimum Set Point,

1. Press the “Set” button for three seconds until “°F” blinks

2. Press the “Up” or “Down” button

3. Press the “Set” button to confirm

The “Set” temperature will blink three times to indicate confirmation. The recommended Minimum Set Point range is 53 - 60°F.

To change the Temperature Differential, see “Advanced Operation” later in this chapter.

To activate and deactivate the “Energy Saver” mode, press the “Energy Saver” button. The

“Energy Saver” indicator light will turn on when the cooling unit is in “Energy Saver” mode

In “Energy Saver” mode, the Minimum Set Point increases 4°F and the Temperature

Differential is unchanged

To activate the “Quick Chill” mode, press the “Up” / “Quick Chill” button for

three seconds

To deactivate “Quick Chill”, press “Quick Chill” button for three seconds again

The “Quick Chill” indicator light will turn on when the cooling unit is in

“Quick Chill” mode

In the “Quick Chill” mode, the cooling unit will run continuously for 6 hours (or until the intake temperature registers 50°F).

This mode is useful after loading “warm” bottles in a cabinet

Advanced Operation of Temperature Controller

Magnum cooling systems can be programmed with advanced settings to achieve more control over conditions inside the cabinet.

Conditions like humidity, the Temperature Differential, and alarm settings all can be modified for custom applications.

To access the advanced settings, do the following:

Press the “Set” button and the “Down” button together at the same time, and hold for three seconds. Then, use the “Up” or “Down”

button to scroll to the following screen:

HUMIDITY:

The factory preset for this setting is “3”.

If the humidity inside the cabinet is too low, press the “Set” button, then use the “Up” button until

the desired setting is reached. The recommended range for this setting is 0-6.

TEMPERATURE DIFFERENTIAL:

The factory preset for this setting is “4”.

When added to the set point, this setting determines the temperature at which the cooling unit will

cycle on. The recommended range for this setting is 4 or 5.