Wine-Mate SSR Series User Manual

Page 26

Advertising
background image

- 25 -

High superheat and normal subcooling

13) Low suction pressure and high head pressure

High superheat and high subcooling

14) Low suction pressure and high head pressure

High superheat and high subcooling

15) low to normal suction pressure and high head

pressure
Normal to high superheat and high subcooling


13) Both evaporator and condenser

restricted; liquid and suction lines
connected wrong

14)

Liquid line restricted before
receiver

15) Condenser restricted


11. Condensing Unit Troubleshooting

Unit not running

1) Incorrect power supply
2) Incorrect or loose wirings
3) Failed

components

4) Low pressure switch shutting down the

system

5) high pressure switch shutting down the

system

1) Check for proper voltage
2) Check all wirings and connections
3) Check start relay, start capacitor,

overload protector, compressor.

4) Check for system restriction or low

refrigerant

5) Check for the condenser fan


























Advertising