Wine-Mate SSV Series User Manual

Page 23

Advertising
background image

- 22 -

The line connection sizes of liquid filter & indicator, the valve

connection sizes of condensing unit and the line connection sizes of
evaporator unit are not necessary the same as the listed refrigeration
line sizes.

If the condensing unit is installed above the evaporator unit, use the

suction line one listed size smaller.

Expansion and solenoid valves have been installed on the liquid line in

the evaporator unit.

1) The installation order starts from condensing unit (including receiver and

discharge valve), liquid line filter-drier, moisture-liquid indicator, liquid line, to
evaporator unit (including liquid line connection, solenoid valve, expansion
valve, and suction line connection), returning to insulated suction line, suction
valve and then back to condensing unit.

2) If the condensing unit is located below the evaporator unit, use inverted U

trap to prevent liquid from flooding back to the compressor; if the elevation
difference is more than 10 ft or the line set exceeds 75 ft, use both inverted U
trap and suction accumulator.

3) If the condensing unit is located more than 10 ft above the evaporator unit,

use U trap to aid oil returning to the compressor.

4) Complete pipe brazing, check solenoid valve and expansion valve restrictions

and test leak.

5) Hook up the drain line and check if water drains.

The line sizes and refrigerant charges are listed as follows.

Model No

Equivalent

Line Set

Liquid

Line

Suction

Line

Drain Line

Recommended

Charge

WM-2520SSV

<= 75 FT

1/4" OD

3/8” OD

7/8” OD

R134a/19 OZ

WM-4520SSV

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/26 OZ

WM-6520SSV

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/32 OZ

7. Connecting Electrical Wires

Connect all electrical components using the wiring diagrams in accordance with
all state and local codes.

8. Evacuating, Charging and Starting the system

CAUTION:
Always use the superheat and subcooling, pressure readings to charge

refrigerant properly; the listed charge amounts are used for reference
only.

If the unit is equipped with a low ambient condition kit and installed in

the summer, charge 15% more refrigerant.

Advertising