Wine-Mate SSVWC Series User Manual

Page 22

Advertising
background image

- 21 -

difference is more than 10 ft or the line set exceeds 75 ft, use both inverted U
trap and suction accumulator.

3) If the condensing unit is located more than 10 ft above the evaporator unit,

use U trap to aid oil returning to the compressor.

4) Complete pipe brazing, check solenoid valve and expansion valve restrictions

and test leak.

5) Hook up the drain line and check if water drains.

The line sizes and refrigerant charges are listed as follows.

Model No

Equivalent

Line Set

Liquid

Line

Suction

Line

Drain Line

Recommended

Charge

WM-2500SSVWC

<= 75 FT

1/4" OD

3/8” OD

7/8” OD

R134a/19 OZ

WM-4500SSVWC

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/26 OZ

WM-6500SSVWC

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/32 OZ


8. Connecting Electrical Wires

Connect all electrical components using the wiring diagrams in accordance with
all state and local codes.

9. Evacuating, Charging and Starting the system

CAUTION:
Always use the superheat and subcooling, pressure readings to charge

refrigerant properly; the listed charge amounts are used for reference
only.


1) Evacuate the system; both discharge and suction valves must be in the

middle positions during evacuating.

2) Charge the system through both suction and discharge valves with refrigerant

using the recommended initial amount; both discharge and suction valves
must be in the middle positions during charging.

3) Turn on the water valve.
4) Turn on the power to start the system and check the following temperatures

and pressures.


10. Adjusting and Completing the installation

1) Set the water regulating valve opening set-point at refrigerant pressure of 120

PSIG. Turn counterclockwise to raise the operating set-point.