MOTOR

FAN GRILLE

MOTOR SHAFT

A

A08505

MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE

SIZE

“A”

IN.

MM

24

6.3

160

30

6.3

160

36

7.3

185

42

7.6

193

48

7.6

193

60

7.6

193

Fig. 16 -- Fan Blade Position

Compressor
Access Panel

Blower
Access
Panel

Control
Access
Panel

A09214

Fig. 17 -- Unit Access Panels

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain

pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean

the coils either before or after each cooling season. Remove all

obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush

attachment. Be careful not to bend the fins. If coated with oil or

grease, clean the coils with a mild detergent and water solution.
Rinse coils with clear water, using a garden hose. Be careful not to

splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On

units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit

base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all

foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or

air filter(s). If the drain trough is restricted, clear it with a
“plumbers snake” or similar probe device.

OUTDOOR FAN

UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit

components.
Keep the condenser fan free from all obstructions to ensure

proper cooling operation. Never place articles on top of the

unit.

CAUTION

!

1. Remove 6 screws holding condenser grille and motor to top

cover.

2. Turn motor/grille assembly upside down on top cover to

expose the fan blade.

3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the

fan off the motor shaft.

5. When replacing fan blade, position blade as shown in Fig.

16.

6. Ensure that setscrew engages the flat area on the motor shaft

when tightening

7. Replace grille.

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panels (see Fig. 17) to locate all the electrical

controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any smoky or burned connections

are noticed, disassemble the connection, clean all the parts, restrip
the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the

access panels (see Fig. 17). Start the unit, and observe at least one
complete heating cycle and one complete cooling cycle to ensure

proper operation. If discrepancies are observed in either or both
operating cycles, or if a suspected malfunction has occurred, check

50V

L

--