Troubleshooting continued-

LED Status

Control Status

Probable Cause

Six flashes‐two 

flashes, three second 

pause (Soft lockout) 

Pressure switch or 

blower temperature 

switch opened 

during burner 

operation. 

System auto resets 

after 5 minutes. 

1. Pressure switch tubing kinked or blocked. 
2. Vent blockage or improper vent configuration. 
3. Vent termination being affected by windy 
conditions. 
4. Blower not spinning up to speed. 
5. Vent temperature too high 
6. Faulty pressure switch or blower temp. switch. 

Six flashes‐three 

flashes, three second 

pause (Soft lockout) 

Pilot flame 

extinguished. 

System resets after 5 

minutes. 

1. Unstable pilot. 
2. Pilot tube blocked or restricted. 
3. Oxidation build up on pilot electrode. 
4. Wire damage to pilot assembly or bad 
connection at gas valve. 
5. Insufficient combustion air. 

Six flashes‐four 

flashes, three second 

pause (Soft lockout) 

Undesired‐false pilot 

flame sensed. 

System auto resets. 

Pilot valve stuck in open position. 

Seven flashes, three 

second pause 

Flammable vapor 

sensor fault 

detected, see 
warning label 

1. Flammable vapor present 
2. Flammable vapor sensor exposed to excessive 
moisture 
3. Flammable vapor sensor exposed to extreme 
ambient temp 

Eight flashes‐one 

flash, three second 

pause 

Flammable vapor 

sensor out of 
specification. 

Possible short. 

1. Flammable vapor sensor out of specification 
2. Possible short 

Eight flashes, two 

flashes, three second 

pause 

Temperature sensor 

fault 

1. Damage to sensor or wire in control’s well. 
2. Control’s sensor resistance out of range. 
3. Replace Control. 

Eight flashes‐three 

flashes, three second 

pause 

Electronics fault 

detected 

1. Verify control is not wet or physically damaged 
2. Reset control on/off switch. 
3. Replace electronic module if 8‐3 error persists 

Eight flashes‐four 

flashes, three second 

pause 

Gas valve fault 

detected. 

1. Verify control is not wet or physically damaged 
2. Reset control on/off switch. 
3. Replace gas control if 8‐4 error persists 