M a i n t e n a n c e, Enclosure mounted leds status indicators, Warning caution warning warning – Chamberlain LM21XP User Manual

Page 12: Maintenance requirements

Advertising
background image

Disable

Yellow

The Yellow LED will light when the door reaches the close
limit and activates a proximity switch attached to terminal
positions 7 and 8 on the release device. This
configuration results in the device not releasing the
fusible link assembly in alarm or power loss situations
and should only be used when the fire door is kept in a
constant closed position.

If the LED does not light when the door reaches the close
limit and activates the proximity switch, then check that
the proximity switch has been activated and that the
switch is set to normally open (N.O.). Check to make
certain that the switch is attached to terminal positions 7
and 8 on the release device.

Power

Red

If the Red LED is lit, then the line power is connected and
switched “on.”

If the LED does not light when power is applied, check
that power is connected as described in the installation
manual electrical connections.

M A I N T E N A N C E

To avoid SERIOUS PERSONAL INJURY or DEATH from
electrocution, disconnect ALL power BEFORE performing

ANY maintenance.

WARNING

CAUTION

WARNING

WARNING

MAINTENANCE REQUIREMENTS

The release device has no scheduled maintenance requirements.
The unit has been designed and tested for use in dry, indoor
locations. Testing of the unit at least once every 90 days is
recommended, but test intervals shall ultimately be subject to
criteria established by the Authority Having Jurisdiction (AHJ).

Mechanical
Reset Plunger

End Link

Front of Release Device

Yellow LED
(Close Door Detection
Release Disabled)

Red LED (Line Power Present)

Bottom of Release Device

Electronic
Reset Button

Test Button

FIGURE 1

ENCLOSURE MOUNTED LEDS STATUS INDICATORS

12

LED Label LED Color

Description

Action Required