Wiring, Preparing for operation – Pilz PNOZ s8 C 24VDC 2 n/o User Manual

Page 5

Advertising
background image

PNOZ s8

Operating Manual PNOZ s8
21400-EN-07

5

Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

The outputs 13-14, 23-24 are safety contacts.

}

Semiconductor output Y32 should

not be used for safety circuits!

}

To prevent contact welding, a fuse should be connected before the output contacts (see

technical details).

}

Calculation of the max. cable length l

max

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

= max. overall cable resistance (see technical details)

R

l

/ km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.

Preparing for operation

}

Supply voltage

Supply voltage

AC

DC

A1
A2

24 V DC

0 V

PNOZsigma

expansion

module

}

Input circuit

Input circuit

Single-channel

Dual-channel

Base unit:

Safety relay PNOZ X

A1
A2

24 V DC

0 V

PNOZsigma

expansion

module

Base unit:

PNOZelog safety relay

Driven via semiconductor

outputs (24 VDC)

A1

A2

0 V

O1

L-

PNOZsigma

expansion

module