Error indicators

Fault

Diagnostics: Internal error, unit defective

}

Remedy: Switch supply voltage off and then on again, change unit if neces-

sary.

Faults - malfunctions

}

Contact malfunctions: If the contacts have welded, reactivation will not be possible after

the input circuit has opened.

Technical details

General

750108

751108

Approvals

CCC, CE, GOST, KOSHA, TÜV,

cULus Listed

CCC, CE, GOST, KOSHA, TÜV,

cULus Listed

Electrical data

750108

751108

Supply voltage

Voltage

24 V

24 V

Type

DC

DC

Voltage tolerance

-20 %/+20 %

-20 %/+20 %

Output of external power supply

(DC)

2,0 W

2,0 W

Residual ripple DC

20 %

20 %

Continuous duty

100 %

100 %

Max. overall cable resistance Rl-

max

Single-channel at UB DC

30 Ohm

30 Ohm

Voltage at

Input circuit DC

24,0 V

24,0 V

Current at

Input circuit DC

65,0 mA

65,0 mA

Number of output contacts

Instantaneous safety contacts

(N/O)

2

2

Inputs

750108

751108

Number

1

1

Semiconductor outputs

750108

751108

Number

1

1

Voltage

24,0 V

24,0 V

Current

20 mA

20 mA