Installation instructions for the charnwood la30ib, Health and safety precautions, Performance – Charnwood LA30iB User Manual

Page 9: Chimney, Hearth, Preparation of fireplace

Advertising
background image

HEALTH AND SAFETY

PRECAUTIONS

Please take care when installing the
appliance that the requirements of the
Health and Safety at Work Act 1974
are met.

Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.

If there is a possibility of disturbing
any asbestos in the course of
installation then please use
appropriate protective equipment.

There must not be an extractor fan
fitted in the same room as the fire as
this can cause the appliance to emit
fumes into the room.

There must be an adequate air supply
into the room in which the appliance
is installed totalling at least 100
square cm. (16 square inches) to
provide combustion air. This is
particularly necessary if the room is
double glazed.

In addition to these instructions the
requirements of BS:8303 and
BS:6461 Pt 1&2; 1984 must be
fulfilled. Local Authority Byelaws
and Building Regulations regarding
the installation of Solid Fuel burning
appliances, flues and chimneys must
also be observed.

PERFORMANCE

The rated output for the LA30iB is
6.1 kW (20,800 btu/h) to water and
2.7 kW (9,200 btu/h) to the room.
These are the outputs obtained during
testing in accordance with BS 3378
burning Sunbrite Doubles with the
doors closed over a 4 hourly
re-fuelling interval.

If the optional boiler reduction brick
is fitted and the deepening bar
removed then the output is reduced to
3.0 kW (10,200 btu/h) to water and
2.1 kW (7,100 btu/h) to the room.

The heat output to the room is
directly proportional to the heat

output to water as shown in Fig. 4.
This means that if the water heating
load is less than the rated output then
the room heating will be reduced by
the same proportion. This must be
borne in mind when calculating the
heating requirements.

CHIMNEY

In order for the appliance to perform
satisfactorily the chimney height must
not be less than 4 metres measured
vertically from the outlet of the
appliance to the top of the chimney.
The chimney should preferably be

175 mm (7 inches) or 200mm (8
inches) internal diameter or square
with sides of 175mm or 200mm
internally and MUST NOT BE LESS
THAN 150mm (6 INCHES)
INTERNAL DIAMETER OR 150 x
150mm INTERNAL SQUARE.

If an existing chimney is to be used it
must be swept and checked, it must
be in good condition, free from
cracks and blockages, and should not
have an excessive cross sectional area
(eg. greater than 250mm x 250mm).
If you find that the chimney is in
poor condition then expert advice
should be sought regarding the
necessity of having the chimney
lined. If it is found necessary to line

the chimney then a lining suitable for
Solid Fuel must be used.

If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS:4543 can be used either internally
or externally. These chimneys must
be fitted in accordance with the
manufacturers instructions and
Building Regulations.

Single wall flue pipe is suitable for
connecting the fire to the chimney but
is not suitable for using for the
complete chimney.

If it is found that there is excessive
draw in the chimney then a draught
stabilizer should be fitted.

HEARTH

The appliance must be installed on a
fireproof hearth and must be situated
at least 300 mm (12 inches) from any
combustible material. The positioning
of the appliance and the size of the
hearth are governed by building
regulations for Class 1 appliances.
These building regulations state that
the hearth must extend in front of the
appliance by at least 300 mm (12
inches) and to the sides of the
appliance by at least 150 mm (6
inches). If in doubt as to the
positioning of the appliance expert
advice should be sought either from
the supplier or the local building
inspector.

PREPARATION OF

FIREPLACE

Before fitting the appliance into an
existing fireplace remove the fireback
and any loose in-fill material.

The hearth, surround and opening for
the appliance must conform with
Figs. 5 and 6. The flat area around
the opening must be a minimum of
750 mm wide and 660 mm high.
Ensure that the hearth and the base in
the opening are flat, level, and at
right angles to the surround.

Make two holes in the chimney

INSTALLATION INSTRUCTIONS FOR THE

CHARNWOOD LA30iB

Boiler

Output

(kW)

Space Output (kW)

0

2.0

4.0

6.0

1.0

2.0

3.0

Output withboiler

fitted

reduction brick

Fig. 4. Performance Chart

Page 7

LA30iB 3.99

Advertising