Leak Test Machine

Due to regulations regarding refrigerant emissions and the difficulties associated with

separating contaminants from refrigerant, Carrier recommends the following leak test

procedures. See

Figure 26

for an outline of the leak test procedures. Refer to

Figure 27

and

Figure 28

during pumpout procedures and

Table 5A

,

Table 5B

,

Table 5C

, and

Table 5D

for

refrigerant pressure/temperature values.

1. If the pressure readings are normal for machine condition:

a. Evacuate the holding charge from the vessels, if present.
b. Raise the machine pressure, if necessary, by adding refrigerant until pressure is at

equivalent saturated pressure for the surrounding temperature. Follow the pumpout

procedures in the

Transferring Refrigerant from Storage Tank to Machine

section,

Steps 1a - e.

Do not use air or oxygen as a means of pressurizing the machine. Some mixtures
of HCFC-22 or HFC-134a and air can undergo combustion.

WARNING

!

WARNING

Click here for Figure 26 — 19XL Leak Test Procedures