Carrier 19XL User Manual

Page 163

Advertising
background image

Note: The oil pump test will not energize the oil pump if cooler pressure is below –5 psig

(–35 kPa).

When the test is finished, or the EXIT softkey is pressed, the test will be stopped and the

Control Test menu will be displayed. If a specific automated test procedure is not completed,

access the particular control test to test the function when ready. The Control Test menu is

described as follows.

*Make sure to Attach to Local Device after changing refrigerant type. Refer to

Selecting

Refrigerant Type

section.

Automated Tests
PSIO Thermistors
Options Thermistors
Transducers
Guide Vane Actuator
Pumps

Discrete Outputs
Pumpdown/Lockout

Terminate Lockout

Refrigerant Type*

As described above, a complete control test.
Check of all PSIO thermistors only.
Check of all options boards thermistors.
Check of all transducers.
Check of the guide vane operation.
Check operation of pump outputs, either all pumps can be
activated, or individual pumps. The test will also test the
associated input such as flow or pressure.
Activation of all on/off outputs or individually.
Pumpdown prevents the low refrigerant alarm during evac-
uation so refrigerant can be removed from the unit; locks
the compressor off; and starts the water pumps.
To charge refrigerant and enable the chiller to run after
pumpdown lockout.
Sets type of refrigerant used: HCFC-22 or HFC-134a.