Modify equipment configuration if necessary – Carrier 19XL User Manual

Page 160

Advertising
background image

If surge prevention occurs too soon or too late:

Modify Amp Correction Factors

To modify the amp correction factor, use the values listed in

Table 7

. Enter the appropriate

amp correction factor in the Service1 table of Equipment Service.

Modify Equipment Configuration If Necessary

The Equipment Configuration table has tables to select and view or modify. Carrier’s certified

drawings will have the configuration values required for the jobsite. Modify these tables only if

requested.

Load

Surge Prevention Occurs
Too Soon

Surge Prevention
Occurs Too Late

At low loads (

<

50%)

Increase P1 by 10 psid (70 kPad)

Decrease P1 by 10 psid
(70 kPad)

At high loads (

>

50%)

Increase P2 by 10 psid (70 kPad)

Decrease P2 by 10 psid
(70 kPad)

Click here for Table 7 — Amps Correction Factors for 19XL Motors