26

Table 2 — CVC/ICVC Display Data (cont)

EXAMPLE 8 — CVC/ICVC_PSWD DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Scroll down to highlight

.or

4. Press .

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations
for the CVC/ICVC only.

EXAMPLE 9 — SETPOINT DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Press .

NOTE: All variables are available for CCN read operation; forcing shall not be supported on setpoint screens.

EXAMPLE 10 — CAPACITY DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Scroll down to highlight

.

4. Press .
5. Scroll down to highlight

.

6. Press .

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screen.

DESCRIPTION

STATUS

UNITS

POINT

Disable Service Password

0-1

DSABLE/ENABLE

PSWD_DIS

**Remote Reset Option

0-1

DSABLE/ENABLE

RESETOPT

Reset Alarm?

0-1

NO/YES

REMRESET

CCN Mode?

0-1

NO/YES

REM_CCN

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Base Demand Limit

40-100

%

DLM

100

Control Point

ECW Setpoint

15-120

DEG F

ecw_sp

60.0

LCW Setpoint

10-120

DEG F

lcw_sp

50.0

Ice Build Setpoint

15-60

DEG F

ice_sp

40.0

Tower Fan High Setpoint

55-105

DEG F

tf2_sp

75

DESCRIPTION STATUS

UNITS

POINT

Entering Chilled Water

–40-245

DEG F

ECW

Leaving Chilled Water

–40-245

DEG F

LCW

Capacity Control

Control Point

10-120

DEG F

ctrlpt

Control Point Error

–99-99

^F

cperr

ECW Delta T

–99-99

^F

ecwdt

ECW Reset

–99-99

^F

ecwres

LCW Reset

–99-99

^F

lcwres

Total Error + Resets

–99-99

^F

error

Guide Vane Delta

–2-2

%

gvd

Target Guide Vane Pos

0-100

%

GV_TRG

Actual Guide Vane Pos

0-100

%

GV_ACT

Target VFD Speed

0-100

%

VFD_IN

Actual VFD Speed

0-100

%

VFD_ACT

VFD Gain

0.1-1.5

vfd_gain

Demand Limit Inhibit

0-100

%

DEM_INH

Amps/kW Ramp

0-100

%

DMD_RAMP

VFD Load Factor

0-200

VFD_LF

MENU

STATUS

CVC

ICVC

SELECT

MENU

SETPOINT

SELECT

MENU

SERVICE

CONTROL ALGORITHM STATUS

SELECT

CAPACITY

SELECT