Table 2 — CVC/ICVC Display Data (cont)

EXAMPLE 19 — SETUP2 DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Scroll down to highlight

.

4. Press .
5. Scroll down to highlight

.

6. Press .

NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.

EXAMPLE 20 — LEADLAG DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Scroll down to highlight

.

4. Press .

5. Scroll down to highlight

.

6. Press .

NOTE: No variables are available for CCN read or write operation.

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Capacity Control

Proportional Inc Band

2-10

gv_inc

6.5

Proportional DEC Band

2-10

gv_dec

6.0

Proportional ECW Band

1-3

gw_ecw

2

Guide Vane Travel Limit

30-100

%

gv_lim

80

Diffuser Control

Diffuser Option

0-1

DSABLE/ENABLE

diff_opt

DSABLE

Guide Vane 25% Load Pt

0-78

%

gv_25

25

Diffuser 25% Load Point

0-100

%

df_25

0

Guide Vane 50% Load Pt

0-78

%

gv_50

50

Diffuser 50% Load Point

0-100

%

df_50

0

Guide Vane 75% Load Pt

0-78

%

gv_75

75

Diffuser 75% Load Point

0-100

%

df_75

0

Diffuser Full Span mA

15-22

mA

diff_ma

18

VFD Speed Control

VFD Option

0/1

DSABLE/ENABLE

vfd_opt

DSABLE

VFD Gain

0.1-1.5

vfd_gain

0.75

VFD Increase Step

1-5

%

vfd_step

2

VFD Minimum Speed

65-100

%

vfd_min

70

VFD Maximum Speed

90-100

%

vfd_max

100

VFD Current Limit

0-99999

Amps

vfdlim_i

250

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Lead Lag Control

LEAD/LAG: Configuration

0-3

leadlag

0

DSABLE=0, Lead=1
LAG=2, STANDBY=3
Load Balance Option

0/1

DSABLE/ENABLE

load/bal

DSABLE

Common Sensor Option

0/1

DSABLE/ENABLE

commsens

DSABLE

LAG % Capacity

25-75

%

lag_per

50

LAG Address

1-236

lag_add

92

LAG START Timer

2-60

MIN

lagstart

10

LAG STOP Timer

2-60

MIN

lagstop

10

PRESTART FAULT Timer

2-30

MIN

preft

5

STANDBY Chiller Option

0/1

DSABLE/ENABLE

stndopt

DSABLE

STANDBY % Capacity

25-75

%

stnd_per

50

STANDBY Address

1-236

stnd_add

93

MENU

SERVICE

EQUIPMENT SERVICE

SELECT

SETUP2

SELECT

MENU

SERVICE

EQUIPMENT SERVICE

SELECT

LEADLAG

SELECT