Installation/operation/maintenance, Warning, Mounting – Beckett 7556 12V GeniSys Control User Manual

Page 3

Advertising
background image

3

GeniSys 12V Control Installation and Operation Manual

Mounting:

Mount the control on a 4” x 4” junction box

on the burner, or inside the equipment

cabinet. In replacement applications,

mount the new control in the same location

as the old control. In some replacement

applications, it may be necessary to rotate

the control on the 4” x 4” box for best fi t.

Mounting orientation: any orientation is

acceptable with the exception of up-side

down.

Installation/Operation/Maintenance

Electrical Shock
Hazard

Electrical shock can cause severe personal

injury or death.

Disconnect ALL electrical power to the

equipment/burner circuit before installing or

servicing this control.
Provide ground wiring to the equipment, burner

and metal control mounting box.
Perform all wiring in compliance with the

National Electrical Code ANSI/NFPA 70

(Canada CSA C22.1).

WARNING

Professional
Service Required.

Incorrect installation or misuse of this control

could result in severe personal injury or death

from heavy smoke, explosion or fi re.

Please read and understand the manual supplied
with this control. This control must be installed,
adjusted and put into operation only by a qualifi ed
individual or service agency that is:

Licensed or certifi ed to install and provide

technical service to oil heating systems.
Experienced with all applicable codes,

standards and ordinances.
Responsible for the correct installation and

commission of this equipment.
Skilled in the adjustment of oil burners using

combustion test instruments.

The installation must strictly comply with all
applicable codes, authorities having jurisdiction and
the latest revision of the National Fire Protection
Association Standard for the Installation of Oil-
Burning Equipment, NFPA 31 (or CSA-B139 and
CSA-B140 in Canada) for stationary equipment.
Regulation by these authorities take precedence
over the general instructions provided in this
installation manual.

WARNING

Explosion, Fire,
Scald, & Burn
Hazard

All heating equipment must have

HIGH LIMIT controls to protect

against excessive temperature

and/or pressure. The control must

interrupt electrical power and shutdown the

burner, if operating or safety controls fail and

cause a runaway condition.

Follow the equipment manufacturer’s wiring

diagrams and note all required safety controls.
Typical safety controls include high

temperature or pressure limits, low water

cutoffs, pressure relief valves and blocked fl ue

sensing switches.
Verify all limit and safety controls are installed

and functioning correctly, as specifi ed by the

manufacturer, applicable safety standards,

codes and all authorities having jurisdiction.
Insure that the equipment is free of oil and oil

vapor before starting or resetting the burner.
Do not wire power directly to the burner

motor. Only wire the motor as shown in

Figure 2. If instant burner heat is required

by the application, purchase or program

a control with a long motor-off delay time,

which will ensure instant heat if a new call

for heat is received within the motor-off

delay time.

WARNING