CONFIGURATION MENU

The Steffes 2100 Series room heating units have a Configuration
Menu, which allows the heaters to be customized to the power
company and consumer’s needs. This menu can be accessed on
start-up and allows configuration settings to be easily adjusted.

Accessing the Configuration Menu

Step 1

Energize the heater. Access to the Configuration Menu is
allowed for the first two (2) minutes of operation. If the
heater has been energized for over two (2) minutes, it
must be powered off and back on again.

Step 2

Press and release the

M button until the faceplate

displays “CONF.”

Step 3

Press the up arrow once and the faceplate will display

“C000.” The display will flash between “C000” and the
corresponding configuration value.

3050 Hwy 22 North

 Dickinson, ND 58601-9413

701-483-5400

 www.steffes.com

“Manufactured in North America”

Part No. 1200286-4

R

R

If access to Configuration Menu times out, the

system must be powered off at the circuit

breaker and back on to re-enter the menu.

Step 4

If necessary, edit the configuration by pressing

and holding the

M button while using the up or

the down arrow button to change the value.

Step 5

Once the value is correct, release the buttons and

press the up arrow button to go to the next
configuration (C001, C002, etc.).

Step 6

Repeat steps 4 through 5 until all configuration

settings have been adjusted to the desired values.

Step 7

Once configured, use the down arrow to leave the

Configuration Menu.

In most applications only a few, if any, configuration changes will be necessary. Following is a description of the
configuration settings and their functions:

Power Line Carrier

(PLC) Peak Control *

Low Voltage Direct Wired Peak Control

Time Clock Module

Peak Control

Line Voltage Peak

Control

Peak Switch Closed for

Charging

Peak Switch Open for

Charging

Configuration

Number

Outdoor

Sensor

No Outdoor

Sensor

Outdoor

Sensor

No Outdoor

Sensor

Outdoor

Sensor

No Outdoor

Sensor

Outdoor

Sensor

No Outdoor

Sensor

C000

5

5 6 5 6 5 6 5 6

C001

60°F

60°F

60°F

60°F

60°F

60°F

60°F

60°F

60°F

C002

20°F

20°F

20°F

20°F

20°F

20°F

20°F

20°F

20°F

C003

Match to the Channel

Selected at PLC

0

0

0

0

0

0

0

0

C004

154

155 154 155 154 159 158 155 154

C005

0

1

1

0

0

0

0

0

0

C006

6

6 6 6 6 6 6 6 6

C007

30

30

30

30

30

30

30

30

30

C008

5°F

5°F

5°F

5°F

5°F

5°F

5°F

5°F

5°F

C009

5°F

5°F

5°F

5°F

5°F

5°F

5°F

5°F

5°F

C010

90°F

90°F

90°F

90°F

90°F

90°F

90°F

90°F

90°F

C011

70°F

70°F

70°F

70°F

70°F

70°F

70°F

70°F

70°F

C012

60°F

60°F

60°F

60°F

60°F

60°F

60°F

60°F

60°F

C013 - C021

Refer to the Time Clock

Installation Instructions

*Factory Default is Power Line Carrier (PLC) Peak Control using Channel 3