Heating element and air channel installation, Ducting, Important – Steffes 3120 Simplified Installation Guide User Manual

Page 2: Warning

Advertising
background image

HEATING ELEMENT AND AIR CHANNEL INSTALLATION

4

WARNING

WARNING

WARNING

WARNING

WARNING

HAZARDOUS VOLTAGE: Risk of electric shock. Can cause

injury or death.
• DO NOT remove electrical panel cover while system is ener-

gized.

• Elements MUST be positioned properly to avoid short circuit-

ing them against any surfaces within system.

• Use care when making connections to avoid element dam-

age.

1. Insert heating elements between brick layers until element ends

embed into side cutouts of brick cavity. The threaded screw tabs on

wire connection terminals should point forward.

2. Install air channel with air deflectors (arrow shaped pieces) facing

inward and narrow ends of deflectors pointing up. Place top of air

channel in first.

3. Lower insulation blankets back into position, one at a time. Tuck

sides into edges, corners and around exposed portions of heating

elements.

4. Install galvanized panel. Slide the top inside the upper lip of top

painted panel. Bottom rests on the outside of the brick cavity.

5. Connect wiring harnesses to heating elements using screws in

element screw kit. Install screws with heads up and threads pointing

down. Tighten screws to 14 in·lbs.

6. Check non-insulated element connections to make sure they do not

come within 1/2" of any surface.

7. Install painted front panel.

DUCTING

5

1. Assemble factory supplied return air plenum

per the instructions provided with the plenum.

2. Once assembled, set plenum on right side of

the system with air filter and indoor coil access

covers facing forward. Line up predrilled holes

on system with holes in flanges of plenum and

attach using screws provided in plenum’s

hardware package.

NOTE: The 3100 series is factory config-

ured for a right-to-left airflow.

3. Insert air filter into filter rack.
4. Connect return air duct to top of plenum.
5. Connect supply air duct in structure directly to

system’s air outlet.

6. If necessary, adjust supply air blower speed by

using the chart below.

7. The W/E jumper MUST be in the ON position or

the blower will not operate with an E call from

the thermostat.

•

When interfacing with a heat pump, the A-Coil MUST
be placed on the return air side.

••••• To maintain a room temperature of 85

o

F or less in the

mechanical room, a 24" x 24" opening can be in-

stalled in the area or a 6" x 6" non-closing register

can be cut into the return air duct. Refer to Place-

ment and Clearance Requirements section of

Owner’s and Installer’s Manual for more information.

10

1

8

"

53

5

8

"

16"

5

3

8

"

HAZARDOUS VOLTAGE: Risk of electric shock. Can cause injury

or death. DO NOT operate the Comfort Plus heating system

without ducting installed to both the air inlet and outlet.

WARNING

WARNING

WARNING

WARNING

WARNING

Fr

on

t A

ir C

ha

nn

el

Fr

on

t

Br

ick

Sid

e

Bo

tto

m

IMPORTANT

System

Top of

27"

1"

812"

1"

22516"

16716"

2618"

17 8"

22716"

External static pressure should not exceed .75 inches water column.

Element-to-Wiring

Harness Connections

Jumper

½ HP Variable

Speed CFM

A 1000
B 1200

C 1400
D 1600