- Page 4 -

C. HPB CONTROL DEVICES & SAFETY LIMIT DEVICES

(TABLE 2)

DEVICE

CONDITION

CATEGORY

NAME

LOCATION

MONITORED

ACTION

Control

Outdoor Air

Outside in a protected

Outdoor Air

Signals to the charge control

Devices:

Temperature

location providing

Temperature

system to set core charge

Sensor

representative outdoor

level in relation to outdoor

air temperatures. (See

temperatures (SeeTable1).

Outdoor Sensor Placement
in Installation Section)

Charge Control

HPB Electrical Section

Core Temperature

Maintains core tempera-

Thermostat

ture level in response to the
outdoor air temperature
sensor.

Low Temperature

Supply Duct (minimum

Supply Air

Modulates HPB mixing

Duct Sensor

of 3' downstream from

Temperature

damper to maintain

HPB supply discharge)

comfortable supply air
temperature (Stage 1
heat call).

Air Discharge

Air Discharge Outlet Port

HPB Discharge

Modulates HPB mixing

Controller

Air Temperature

damper to maintain
maximum HPB dis-
charge air temperature
(Stage 2 heat call).

130

o

Low Core

See Figure 10

Core Temperature

De-energizes HPB

Temperature

blower below preset

Switch

temperature
(See Table 3).

Safety

Core Charging High

HPB Limit Bar (See

Core Temperature

De-energizes HPB

Devices:

Limit Switches:

Figure 9)

resistance heating

(3) each HPB11B

elements.

(4) each HPB15B
(6) each HPB22B

Air Discharge

Air Discharge Outlet

HPB Air Discharge

De-energizes HPB

High Limit

Port

Temperature

blower when discharge
air exceeds 190

o

F.

Slam Gate

Air Discharge Outlet

HPB Air Discharge

At air discharge

Port

Temperature

temperature of 212

o

F,

fusible melt link re-
leases slam gate,
positively blocking
discharge air. All HPB
electrical functions de-
energized.