E. HPB CORE CHARGING CONTROL STRATEGY

(TABLE 4)

STAGE 2 HEAT CALL

MODE

STAGE 1 HEAT CALL

(EMERGENCY HEAT)

AIR CONDITIONING CALL

On-peak without

No core charging.

No core charging unless

No provision for

compressor control

override activated, then

core charging.

(above 45

o

F outdoor

Level 1 core charge.

air temperature)

Off-peak without

No core charging.

Core heating elements

No provision for

compressor control

activated to provide

core charging.

(above 45

o

F outdoor

Level 1 charge.

air temperature)

On-peak without

Core heating elements

Core heating elements

No provision for

compressor control

energized to provide

energized to provide

core charging.

(above 45

o

F outdoor

Level 1 charge only if

Level 1 charge only if

air temperature)

override activated.

override activated.

Off-peak with

Core heating elements

Core heating elements

No provision for

compressor control

energized to provide

energized to provide

core charging.

(above 45

o

F outdoor

Level 1 charge.

Level 1 charge.

air temperature)

On-peak (any out-

Core heating elements energized to provide Level 1

door air temper-

charge, with or without heat call; but, only if on-peak

ature below 45

o

F)

override activated. Charge input of the HPB11 and HPB15
is limited to 7.3 kW. Charge input of the HPB22 is
limited to 10.9 kW.

Off-peak (outdoor

Core heating elements energized to provide Level 1 charge,

air temperature of

with or withour heat call.

45

o

F)

Off-peak (outdoor

Core heating elements energized to provide Level 2

air temperature

core charge, with or without heat call. All core heating

of 35

o

F)

elements energized.

Off-peak (outdoor

Core heating elements energized to provide Level 3

air temperature

core charge, with or without heat call. All core heating

of 25

o

F)

elements energized.