MAXX 6T Owner’s Manual

Page 101

Removing the Degraded Drive from the RAID Unit

Figure 43 - Removing Failed Drive from Array

The UNIT MAINTENANCE SCREEN above will appear.

• Remove the degraded drive from the menu by clicking Remove Drive.

• Select the Rescan Controller option on the above screen to have the system recognize the

drive as Available.