Basic Operation

AlphaServer Intelligent Peripheral Platform Hardware Owner's Guide 3–5

5.

Remove the three screws from the top edge and the three screws from the bottom edge of
the alarm indicator panel frame that secure the alarm indicator panel rear cover.

6.

Remove the alarm indicator panel rear cover.

7.

Remove the seven batteries from the battery holders.

___________________________ WARNING _________________________

Replace the batteries with the same type (PN 12-41230-04) or an equivalent
type recommended by the battery manufacturer. Danger of explosion exists if
batteries are incorrectly replaced. Discard used batteries according to
battery manufacturer instructions. Be certain to follow any applicable
country, state, or local statutes for proper battery disposal.

______________________________________________________________

___________________________VORSICHT _________________________

Ersetzen Sie die Batterien nur durch Batterien des gleichen (PN 12-41230-04)
oder ähnlichen Typs, so wie es vom Hersteller empfohlen wird. Wenn Sie die
Batterien falsch auswechseln, besteht Explosionsgefahr. Folgen Sie bei der
Beseitigung der alten Batterien sowohl den Anweisungen des
Batterieherstellers als auch den jeweiligen länderspezifischen bzw. lokalen
Vorschriften zur richtigen Batteriebeseitigung.

______________________________________________________________

8.

Observing proper polarity, install the seven new batteries in the battery holders.

After installing the new batteries, reverse steps 1 through 6.

3.3.1.2 Dry Contacts

The dry contacts terminal connectors (see Figure 3-2) are located on the rear panel of the
alarm display unit. The four contacts on the input terminal block correspond to Critical,
Major, Minor, and Audio Shut-off alarm inputs. The output terminal block contacts
correspond to Critical, Major, Minor, and Audio Shut-off alarm outputs. These terminal
blocks can be used to connect remote alarm indicators. When an alarm condition occurs, the
corresponding relay is closed to connect a voltage on the input terminal to a remote alarming
device on the output terminal. See Table 3-1 for the dry contact relay functional specification.
Additionally, an audible alarm can be remotely disabled by connecting to the Shut-off Alarm
contacts. Refer to Appendix A for the dry contact electrical specifications.