D
GB
F
E

19

96098-11.2014-DGbFE

5| Electrical connection

5.6 External connection of the MP 10 for terminal boxes at reduced height (Accessories)

Terminal box

PTC1

PTC2

1

2

3

4

3

4

PE

R2

The compressor and the trigger unit MP10 are operational when the H3 LED (green) illuminates.

X3:

5.7 Function test of the trigger unit MP 10

Item

Procedure

LED H1 LED H2 LED H3

Red

Red

Green

1

Power supply interrupted (L1 or S1)

OFF

OFF

OFF

Release the motor temperature sensor connection (1 or 2)

Release the hot gas temperature sensor (if installed) (3 or 4)

2

Restore the power supply (L1 or S1)

ON

Function check of motor temperature sensor: operational

ON

Function check of hot gas temperature sensor: operational

ON

3

Power supply interrupted again (L1 or S1)

OFF

OFF

OFF

Reconnect terminals 1 or 2 and/or 3 or 4

4

Restore the power supply (L1 or S1):

OFF

OFF

ON

MP 10 is operational again

Before start-up, troubleshooting or making changes to the control power circuit,
check the functionality of the trigger unit:

Fig. 23

0.5 mm²