18. Now the ORB is ready to work on your network.

19. Close the browser to log out of the ORB.

20. Change the computer IP address back to the original - this is the IP address written down in Step 5

(See Steps 1-5 to access the address location again)

CREATE A RECORD TABLE

NOTE: Each device on a serial network must have a unique serial address. Each product can be set differently,
refer to the Installation & Operation manual for individual products. The table below can be used to capture the
required data for each device, add rows as needed.

SILO DESCRIPTION

PRODUCT NAME (MODEL)

SERIAL ADDRESS (DECIMAL)

Sample: North silo

Yo-Yo

000

TO SET UP THE VESSELS IN THE ORB

1. Log in to the ORB normally using a web browser.

User Login = Admin

Password = Admin

2. Scan for devices

a. Go to the NETWORKING tab

b. Click Set Up Serial Ports

c. Choose the Port that corresponds with the wiring of the ORB, click Configure

d. Choose the setting that matches the jumper setting (RS-485/MODBUS or KM/RS-422), click Update

e. Choose Manually Add Devices

f. Locate each serial address block (reference record table if required), click SCAN

g. Click continue, repeat until all devices have been successfully added. The ORB is now ready to

begin taking readings.

3. A company administrator should be set up, as well as, any additional user profiles. See Using the ORB,

Section VII for detailed instructions.