VIII. TROUBLESHOOTING

PROBLEM

POSSIBLE CAUSE

SOLUTION

Power On LED is off

Power Switch Off

Turn power On

10/100 Light On

10M bit connection

No problem

Network cable not connected

Connect Network cable

Device Not Displayed on
Main page

Page not setup to display all devices

Click edit View and update view, adding devices

An action is greyed out

Permission not setup

Administrator must manage users and roles to give the permission
required.

No communication to
Devices

Jumpers set incorrectly on ORB PCB

Setup jumpers per page 8, 9

Wiring incorrect

Correct wiring per page 8, 9

Com port not setup correctly

Click setup serial ports and correctly setup the serial port being used

Broken serial cable

Do a continuity check or serial cable

Device power off

Check power on each device

Damaged ORB serial port

Login as an Admin, click setup serial ports and run the loop back
test. See Figure 4 for wiring of loopback

120 Ώ End of Line Resistor not

installed for Modbus

See wiring per page 9

Unable to connect to ORB

Incorrectly set IP address

Short pins 2 and 3 of the service DB9 serial port during a power
cycle to set the IP address back to 192.168.1.170

Figure 4. Wiring for Loop Back Tests

RS-485

RS-422

16

16

97-1167-01 Rev. J