MC2: 04/23/13 Page 23 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

BIAS DIP

SWITCHES

NOTE:

THE BIAS DIP SWITCHES CAN BE ACCESSED

FROM THE WIRING COMPARTMENT WITHOUT

REMOVING THE FRONT PANEL FROM THE UNIT.

WIRING COMPARTMENT

Figure 2-6: Location of ACS DIP Switches

2.7 RS485 (MODBUS) WIRING, BIAS, AND TERMINATION AT

AERCO BOILERS

The RS485 wiring connections at the AERCO Boilers will depend on the type of AERCO Boilers

and Control Systems being used on the Modbus Network. Benchmark Series and KC1000

Boilers currently utilize C-More Control Systems. Modulex Series Boilers utilize Boiler Control

Modules (BCMs) with E8 Controllers.

2.7.1 RS485 Wiring, Termination& Bias for Benchmark Series and KC1000 Boilers

RS485 wiring connections are made at the RS485 terminals of each boiler’s I/O Box (

Figures 2-

7 or 2-8). However, activating bias and loop termination can be performed using one of two

available methods as described below in

Method A and on the following page in Method B.

Where possible,

Method B is the preferred method.

Method A: For Method A, the bias switches in the ACS are left in the deactivated (up) position.

Bias and termination are controlled at the boiler end of the RS485 loop by activating the bias

and termination DIP switches on the PMC board of the last C-More Control Box on the daisy-

chain. Refer to

sheet 1 of Figure 2-7 (Benchmark), or Figure 2-8 (KC1000) and proceed as

shown below: