4 operating menu, 1 header temp and percent of load, 2 header setpoint – AERCO Control System (ACS) User Manual

Page 47: 3 outside air temp, Header temp and percent of load, Header setpoint, Outside air temp, Gf-131 aerco control system (acs)

Advertising
background image

MC2: 04/23/13 Page 47 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

NOTE

Paragraphs 3.4 through 3.12 provide detailed descriptions of the

options contained in each of the menus shown in

Figure 3-2. The menu

options appear in the first line of the VFD display and the corresponding

value or setting for the displayed option will appear in the second line of

the display.
Refer to

Appendix A for tabular summaries of all menu options showing

the allowable entry ranges and default values.

3.4 OPERATING MENU

The Operating Menu displays a number of key operating parameters for the ACS: These

parameters include:
HEADER TEMP, HEADER SETPOINT, OUTSIDE AIR TEMP, PERCENT OF LOAD, I/O

STATUS and RETURN TEMP (with optional Temperature Sensor).
All of the items in this menu are “Read-Only” and do not allow personnel to change or adjust

any of the displayed parameters. Since this menu is “Read Only”, it can be viewed at any time

without entering a password. The Operating Menu options are described in the paragraphs

which follow.

3.4.1 HEADER TEMP AND PERCENT OF LOAD

The HEADER TEMP menu option displays the actual water temperature (°F) measured by the

Header Sensor connected to HDR SEN terminals 4 and 5 of the ACS. If the Header Sensor is

not installed, HDR SENS ERROR will appear in the first line of the display.

The red FAULT

indicator will also light. The Header Sensor

MUST be installed for the ACS to operate properly.

The PERCENT OF LOAD option shows the percent level going from the ACS to each boiler in

the boiler plant. It also shows the number of boiler units that are operating.

NOTE

The ACS will shut down the last boiler firing when the Percent Output

Level goes below the BLR STOP LEVEL. The shutdown will be

indicated by the second line of the default display flashing. By the same

token, as the Percent Level Output rises from 0%, the second line of the

default (Operating Menu) display will flash until it reaches the BLR

START PERCENT and the Header temperature is below 'Setpoint -

DEMAND OFFSET.

3.4.2 HEADER SETPOINT

This menu option is the setpoint temperature to which the control is set when operating in the

Constant Setpoint, Remote Setpoint or Outdoor Reset Mode. When in the Constant Setpoint

Mode, this value is equal to the Internal Setpoint setting in the Configuration Menu. When in the

Remote Setpoint Mode, this value is the setpoint equivalent to the remote analog signal or

Modbus value supplied to the unit. When in the Outdoor Reset Mode, this is the derived value

from the charts in

Appendix D.

3.4.3 OUTSIDE AIR TEMP

The OUTSIDE AIR TEMP option shows the outdoor air temperature (°F) measured by the

Outdoor Air Sensor. This sensor is connected to OUT AIR SENS terminals 1 and 2 of the ACS.