Appendix a – AERCO BMS 168 User Manual

Page 50

Advertising
background image

A-2

Appendix A

(cont.)

________________________


CURRENT LOOP

Input resistance

250 Ohms

Protection

Isolated from AC line potential, fuse-protected at
62 mA, open loop detected at <1 mA

Operational current range

4 mA to 20 mA


SET BACK

Input

12 VDC at 15 mA. External short activates circuit;
Open deactivates it


OUTPUTS


SYSTEM START RELAY

Contact Rating

120 VAC at 5 A, fuse protected at 5 A

Operation

Relay closes when outside air temperature is less
than the system start temperature setting


FAULT ALARM RELAY

Contact Rating

120 VAC at 5 A, fuse protected at 5 A

Operation

Relay closes when valid error condition occurs

AUXILIARY RELAY

Contact Rating

120 VAC at 5 A, fuse protected at 5 A

Operation

Relay closes when all available boilers are
operating at maximum power input (fire rate).
Relay can be programmed to close when all
available boilers are at maximum power input or
no boilers are available (all boilers faulted or
turned off).